Wire gauge and ampacity calculator

The smallest AWG or kcmil conductor that carries a load after NEC ambient and conductor-count derating, with the full ampacity table for the chosen column.

Units
Presets
A
Load current. Multiply a continuous load by 1.25 first (210.19(A)(1), 215.2(A)(1)).
Use the lowest rating of the wire and its terminations.
°C
In the same raceway or cable. Above 3, Table 310.15(C)(1) applies.
Smallest copper conductor, 75 °C column
8 AWG
Table 310.16, 50 A before correction.
8 AWG copperØ 3.26 mm8.366 mm²12 AWG, referenceØ 2.05 mm
Equivalent solid conductor, to scale beside 12 AWG. Stranded conductors are larger overall.
Allowable ampacity after correction
44 A
Load as share of allowable
90.9 %
Conductor area
8.366 mm²
Ambient correction factor
0.88
Adjustment for conductor count
1
Copper, 75 °C, Table 310.16 raceway or cable
SizeArea (mm²)Table (A)Corrected (A)
14 AWG2.0812017.6
12 AWG3.3092522
10 AWG5.2613530.8
8 AWG8.3665044
6 AWG13.36557.2
4 AWG21.158574.8
3 AWG26.6710088
2 AWG33.63115101
1 AWG42.41130114
1/0 AWG53.48150132
2/0 AWG67.43175154
3/0 AWG85.03200176
4/0 AWG107.2230202
250 kcmil126.7255224
300 kcmil152285251
350 kcmil177.3310273
400 kcmil202.7335295
500 kcmil253.4380334
600 kcmil304420370
700 kcmil354.7460405
750 kcmil380475418
800 kcmil405.4490431
900 kcmil456520458
1000 kcmil506.7545480
1250 kcmil633.4590519
1500 kcmil760.1625550
1750 kcmil886.7650572
2000 kcmil1013665585
Method

How this is calculated

I_allowed = I_table × F_ambient × F_count
I_table   NEC Table 310.16 (raceway, cable, earth) or 310.17 (single conductor, free air)
F_ambient NEC Table 310.15(B)(1)(1), 30 °C basis
F_count   NEC Table 310.15(C)(1): 4 to 6 = 0.80, 7 to 9 = 0.70, 10 to 20 = 0.50,
          21 to 30 = 0.45, 31 to 40 = 0.40, 41 and above = 0.35
Result    smallest size with I_allowed ≥ load
Tables
Table 310.16 covers up to three current-carrying conductors in raceway, cable or earth at 30 °C. Table 310.17 covers single insulated conductors in free air at 30 °C. Both run to 2000 kcmil, from 14 AWG for copper (18 AWG in the 90 °C column) and 12 AWG for aluminum.
Ambient
Bands are whole degrees; a fractional ambient uses the next band up. Where the table shows no factor (for example 60 °C wire above 55 °C ambient) the rating is not permitted.
Small conductors
NEC 240.4(D) limits the overcurrent device to 15 A on 14 AWG, 20 A on 12 AWG and 30 A on 10 AWG copper, and 15 A and 25 A on 12 and 10 AWG aluminum, whatever the table ampacity. 18 and 16 AWG copper are limited to 7 A and 10 A, with conditions on the load and the protective device.
Not included
The 125 % continuous-load factor, termination temperature limits (110.14(C)), rooftop adders and voltage drop. Chassis and aerospace bundle ratings (SAE AS50881) are not included: their published curves could not be verified to a primary source.
FAQ

Questions

In copper at 30 °C with up to three current-carrying conductors, 10 AWG: Table 310.16 gives it 30 A in the 60 °C column and 35 A at 75 °C. NEC 240.4(D) allows a 30 A breaker on 10 AWG copper. In aluminum, 10 AWG is 30 A at 75 °C but 240.4(D) limits it to a 25 A device, so a 30 A circuit takes 8 AWG.

Only for derating. NEC 110.14(C) caps the ampacity at the lowest rated termination, and equipment rated 100 A or less, or marked for 14 to 1 AWG, is 60 °C unless listed otherwise. Start from the 90 °C value, apply the ambient and count factors, then check the result does not exceed the 60 or 75 °C table value for that size.

Table 310.15(B)(1)(1) multiplies a 75 °C conductor by 0.88 at 36 to 40 °C and by 0.75 at 46 to 50 °C. 8 AWG copper at 75 °C drops from 50 A to 44 A at 40 °C. 60 °C insulation is not permitted above 55 °C ambient.

Above three current-carrying conductors in one raceway or cable, Table 310.15(C)(1) cuts every conductor to 80 % (4 to 6), 70 % (7 to 9) or 50 % (10 to 20). Nine 12 AWG THHN conductors at 90 °C carry 30 × 0.70 = 21 A each.

Single conductors in free air use NEC Table 310.17, which this calculator includes. Bundled harness derating to SAE AS50881 is not included because its curves could not be verified here; for bundles inside equipment, 310.16 with the conductor-count adjustment is the conservative choice.