Conduit fill calculator

Fill percentage, pass or fail and the maximum conductor count for a raceway, from the NEC Chapter 9 tables for each conduit type.

Units
Presets
Include equipment grounding conductors (Note 3).
Fill, 3/4 in EMT
22.5%
Within the 40 % limit.
Fill22.5 %Limit40 %, Chapter 9 Table 1PassRaceway, inside Ø3/4 in EMT, 20.9 mmConductors, Ø over insulation9 × 12 AWG THHN, 3.31 mm
Section to scale: inside diameter from Table 4, conductor diameters from Table 5. Illustrative arrangement.
Check inputs
  • If more than three of these carry current, apply the ampacity adjustment of NEC 310.15(C)(1). Equipment grounding conductors count toward fill but not toward that adjustment.
Result
Pass
Most 12 AWG THHN, THWN, THWN-2 that fit
16
Smallest EMT for 9 conductors
1/2 in (16)
Conductor area, total
77.23 mm²
Raceway internal area
343.9 mm²
EMT (Article 358), 9 × 12 AWG THHN, THWN, THWN-2
Trade sizeMetricArea (in²)Allowed (in²)Max conductorsFill
1/2 in160.3040.122939.4 %
3/4 in210.5330.2131622.5 %
1 in270.8640.3462613.9 %
1-1/4 in351.4960.598458 %
1-1/2 in412.0360.814615.88 %
2 in533.3561.341013.57 %
2-1/2 in635.8582.341762.04 %
3 in788.8463.542661.35 %
3-1/2 in9111.544.623471.04 %
4 in10314.755.94430.811 %
Method

How this is calculated

Fill = n × A_wire / A_raceway
Limit: 53 % for 1 conductor, 31 % for 2, 40 % for more than 2     (Table 1)
       60 % for a nipple of 24 in. (600 mm) or less                 (Note 4)
Max n = A_raceway × limit / A_wire, a decimal of 0.8 or more rounds up (Note 7)
Raceways
Table 4 total internal areas for EMT (Art. 358), IMC (342), RMC (344), PVC Schedule 40 and 80 (352), FMC (348) and LFMC (350), 3/8 to 6 trade size where listed.
Conductors
Table 5 approximate areas including insulation: THHN, THWN, THWN-2 (14 AWG to 1000 kcmil); XHHW, XHHW-2, XHH and THW, THW-2, THHW, TW (14 AWG to 2000 kcmil). Values are for concentric stranding; compact conductors (Table 5A) are smaller.
Count
Include equipment grounding and bonding conductors (Note 3). Note 7 rounding applies only when all conductors are the same size, which is the case this calculator handles. It is applied at every count, including the case Note 7 names of one conductor at 0.8 or more, so a passing fill can sit slightly above the percentage; the result says when it does.
Edition
Table 1 and its notes are checked against the NFPA 2026 cycle First Draft, which reproduces the 2023 text with proposed edits, and against the 2017 edition. Table 4 and Table 5 values are checked against the 2017 edition, the latest full text that could be read; they are not known to have changed.
FAQ

Questions

16. Table 4 gives 3/4 in EMT 0.533 in² and Table 5 gives 12 AWG THHN 0.0133 in². At 40 % that is 0.2132 / 0.0133 = 16.03 conductors.

NEC Chapter 9 Table 1 sets 40 % for more than two conductors so they can be pulled without damage and can shed heat. One conductor may fill 53 % and two only 31 %, because two round conductors can jam across the diameter.

Yes. The wall is thicker, so 1 in Schedule 80 has 0.688 in² inside against 0.832 in² for Schedule 40, about 17 % less. At 40 % that is 20 against 25 conductors of 12 AWG THHN.

Yes. Chapter 9 Note 4 allows 60 % for a nipple of 24 in. (600 mm) or less between boxes or enclosures, and the 310.15(C)(1) adjustment factors need not apply to it.

Related